Product Description
Medical gases controlling equipment for oxygen pipeline system
Second grade pressure reducing valve box is also integrated with the pressure pipe and cut-off function, the purpose of decompression is pipeline pressure control in a certain pressure
range, such as for ward the oxygen pressure control in about 0.3~0.5Mpa for hyperbaric oxygen
chamber pressure control in about 0.6~ 0.8MPa and from the bus or liquid oxygen tank output
pressure is generally in the 0.8~1.0Mpa left and right.
In the use of gas in the region to set up two level decompression device, but also can play the
role of buffer pipe pressure, reduce the impact on the patient, reduce the application risk.
Vacuum suction system and AGSS system without the need for decompression, and oxygen,
compressed air, nitrous oxide and other medical gases generally need to set the second grade
pressure reducing device in the pipeline. The function of the main function is to achieve the
opening and closing of the pipeline.
Our products with wall mounted box, namely all the pressure reducer and cut-off valve installation there can be multiple gas piping layout in a box . The box body is fixedly
mounted on the wall and connected to the gas line.
Each gas pressure indicator, through the front of the organic glass form observed pressure value
Box of the button switch, usually in a locked state and need to maintenance or operation,
press the "lock" and the box body can be opened easily.
For oxygen, set up a dual channel, when a failure occurs, you can immediately close the road,
open the bypass air, to ensure that the gas can continue to supply.
The first single gas pressure regulator, after decompression can be read easily on the pressure gauge.
Can be connected with gas alarm box (need to install electric contact pressure gauge)